Key Points at a Glance
- A plant in Italy generates its compressed air with an SCC STRONG 2S 132: a two-stage, variable-speed rotary screw compressor with an IE5 permanent-magnet motor and 132 kW rated power.
- According to the project team, the focus was on the electrical power input of compressed-air generation.
- According to the project team, the installation fully met the customer’s expectations.
- The right efficiency benchmark is specific power in kW per m³/min – not rated power.
- Such values are only comparable at the same pressure, a comparable operating point, and the same system boundary.
Starting point: compressed air with as little electricity as possible
Compressing air requires energy. With an electrically driven compressor, this results in electricity costs. For the new compressed-air generation at a plant in Italy, the project team therefore focused on electrical power input.
The right benchmark is not the motor power on the nameplate, but specific power. It relates the electrical power input of the entire compressor package to the delivered volumetric flow. This is stated as free air delivery (FAD) under defined reference conditions. The unit of specific power here is kW per m³/min.
The solution: a STRONG 2S 132
An SCC STRONG 2S 132 was installed. The series combines several features designed for low specific power:
- Two-stage compression: The air is compressed in two stages and cooled in between. This can reduce energy demand compared with single-stage compression.
- IE5 permanent-magnet motor: according to the product documentation, air-cooled, without an additional oil circuit for motor cooling.
- Two variable frequency drives: The main motor adjusts its speed to air demand, and the fan to cooling demand.
- Direct drive: no V-belt between the motor and the compression stage.
- SCC-C80 controller: according to the product documentation, displays power draw and cumulative energy demand.
Project snapshot
SCC STRONG 2S 132 at a plant in Italy
| Feature | Specification |
|---|---|
| Location | Plant in Italy |
| Compressor | SCC STRONG 2S 132 |
| Design | Oil-injected, two-stage rotary screw compressor |
| Rated power | 132 kW |
| Free air delivery range according to catalog | 9.90–26.39 m³/min at 8 bar; 8.90–23.69 m³/min at 10 bar |
| Motor | IE5 permanent-magnet motor, air-cooled |
| Control | Frequency inverter for main motor and fan |
| Drive | Direct drive |
| Controller | SCC C80 |
| Warranty | 5 years according to the valid warranty terms, details on request |
The FAD values are catalogue figures for the series in accordance with ISO 1217 for the 8 and 10 bar pressure variants. They describe the machine’s control range, not the operating pressure or the actual on-site FAD.
Result: customer expectations met
After installation, the project team reported that the STRONG 2S 132 fully met the customer’s expectations. How efficiently a system performs in day-to-day operation is shown by specific power – determined at the actual operating point and under the same conditions used for comparison.
How to interpret specific power
Specific power is a ratio: electrical power input divided by FAD, both determined at the same operating point. A calculation example with assumed values, independent of this project: If a compressor draws 100 kW at 8 bar and delivers 16 m³/min, its specific power is 6.25 kW per m³/min.
If you want the energy demand per cubic metre, convert to kWh per m³: power divided by the hourly delivered volume. In the example, that is 100 kW divided by 960 m³/h, i.e. around 0.104 kWh per m³.
The figure “kW per m³” is incomplete for specific power. What is meant is the ratio of electrical power input to volumetric flow, stated here in kW per m³/min. The energy demand per cubic metre produced, by contrast, is stated in kWh/m³.








What Other Facilities Can Adopt
- Compare by specific power, not by rated power. Two compressors with the same motor power can require different amounts of electricity for the same cubic metre. This is also shown by the application example “Why 55 kW is not the same as 55 kW”.
- Insist on the same conditions. Only compare values at the same pressure, a comparable operating point, and the same system boundary. Ask whether variable frequency drives, fan and controller are included, which reference conditions the FAD refers to, and which test method was used, e.g. ISO 1217.
- Measure your own system. Record the active power input of the entire compressor and the FAD simultaneously under real load, over a representative period. The article Measuring compressed-air consumption explains how to do this.
- Translate differences into costs. An example calculation with assumed values: a difference of 0.5 kW per m³/min results in around 40,000 kWh per year at 20 m³/min and 4,000 full-load hours. Multiply this by the electricity price to obtain the additional costs. A separate article shows how to determine compressed-air costs per m³.
How another plant in Italy selected its compressor specifically based on efficiency features is shown by the project on energy-efficient compressors in the STRONG 2S series.
Frequently Asked Questions
What does specific power mean for a compressor?
It describes the ratio of electrical power input to free air delivery (FAD) and is stated in kW per m³/min. The lower the value at the same pressure, a comparable operating point, and the same system boundary, the more efficiently the machine operates.
How do you convert kW per m³/min to kWh per m³?
Divide the value by 60. The 6.25 kW per m³/min in the calculation example above thus becomes around 0.104 kWh per m³. Both values apply only to the operating point at which power and FAD were determined.
Does the compressed-air dryer belong in the calculation?
Not in the compressor’s specific power: dryers and further treatment have their own system boundary and are assessed separately. If you relate the energy consumption of the compressor and treatment to the same usable compressed-air volume with the same reference conditions, the shares can be added in kWh/m³. The electricity cost per cubic metre is only obtained when you multiply this value by the electricity price.
Make your compressed-air generation more efficient
Would you like to know what specific power is realistic for your application? Tell us the required pressure at the point of use, the required FAD, your operating hours and—if available—measurement data on power and volumetric flow. As part of the compressed-air consultation, SCC air compressors will check which series and which control concept fit your load profile. We will also be happy to explain the warranty terms.